Furnace Fault Codes

Goodman furnace E9: High stage pressure switch stuck open

E9 means the second-stage pressure switch did not close when the furnace called for high fire. Low-stage heating usually still works, so the symptom is a furnace that heats but never reaches full output.

Applies to: Goodman GMVC96, GMVM97, GCVC96, GCVM97 and Amana AMVC96, AMVM97 two-stage and modulating gas furnaces with a two-character alphanumeric display. Older two-stage boards report the equivalent condition as nine flashes.

What it means

When a two-stage furnace steps up to high fire it moves more combustion air, and a separate pressure switch must close to prove that draft. E9 means it did not. The practical consequence is distinctive and easy to misread: the furnace is not dead. It runs on low fire, which in mild weather may be perfectly adequate, so the fault often goes unnoticed until it turns cold. A furnace that used to satisfy the thermostat and now runs continuously without reaching setpoint is the usual way people meet this code — and by then the underlying restriction has often been developing for weeks.

Most common causes

How to diagnose it

  1. Note whether the house heats slowly rather than not at all. That pattern fits this fault and rules out several others.
  2. Check the outside vent termination. A partial restriction is precisely what produces a high-stage-only failure.
  3. Check the condensate drain for slow drainage rather than complete blockage.
  4. Note whether the fault followed a service visit, since swapped switches are a genuine and easily missed cause.
  5. Confirm the furnace is two-stage or modulating; a single-stage model showing this means the code has been misread.

How to fix it

  1. Clear the vent termination and condensate drain if either is restricted. Both are within homeowner reach and both cause this.
  2. The pressure switches, hoses, and inducer are technician work.
  3. Have the technician confirm the switches are fitted the right way round if the furnace was recently serviced.
  4. Do not simply live with low fire and ignore the code. The partial restriction that causes it usually worsens, and eventually it affects low fire too.

Notes

A furnace stuck on low fire is easy to tolerate in mild weather and impossible in a cold snap. Acting when the code appears rather than when the house stops keeping up is typically several weeks and one weather change cheaper.

Related

Sources

This site is a reference, not a substitute for a licensed HVAC technician. Gas appliances can leak carbon monoxide and cause fire. Anything involving gas lines, the heat exchanger, or the flame sensing circuit should be handled by a licensed professional. Pages are written with AI assistance from the sources listed on each page and checked against them before publishing.